Conettix D6600 Manual de usuario Pagina 76

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 185
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 75
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
76
Table 92: X-SIA Printer/LCD output
Characters Description
MM/DDsHH:MM Date and time.
Lxx Line number.
SIA SIA format.
AAAA Account code.
E SIA block code.
MM SIA event code.
ZZZZ Zone number.
* Text identifier.
Single quote.
TTT…T 13 character text string.
Single quote.
NM Unit field characters.
3.2.32 SafeCom (Message Type p)
SafeCom
Example
SIA Mode Description
<LF><CRC><p><sequence#><receiver#><line#>[#aaaa|EEEEdata]<CR>
Table 93: SafeCom (Message Type p) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message p
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits: 01 to 99 for
D6600.
line# The line number of the line in the receiver gateway that sent the message.
Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
account # The communicator's account number has four digits.
EEEE Event code, four digits.
data Event code parameter data.